3125A 5000V Megohmeter Handheld Insulation Resistance Tester

1.Designed to meet the following safety standards:

IEC 61010-1,-2-30 (CAT III 600V/CAT IV 300V Pollution degree 2);

IEC 61010-031 (Requirements for hand-held probes);

2.With auto-discharge function:

When an insulation resistance like a capacitive load is measured, electric charges stored in capacitive circuits are automatically discharged after the measurement. Discharge can be checked on the voltage monitor.

3.Backlight function to facilitate working at dimly illuminated location or at nighttime work.

4.Bar graph display;

5.Audible and visible LIVE circuit warning;

6.With Auto-power off function:

The instrument automatically will turn itself off if there is no function change or button press for 10 min to conserve battery power.

7.Auto-measurement and display of PI (Polarization Index), DAR(Dielectric Absorption Ratio);

分类: 标签:

描述

3125A Handheld Insulation Resistance Tester

Insulation testing is very important to ensure the quality of products and the safety of people and equipment in operation.

Before adding power to the system, the insulation test is used to verify that it is sound and can improve the performance of the system. Insulation test can find manufacturing process problems and equipment defects, which can not be found before the equipment fails. In the European Union, the test is mandatory, even for the smallest civilian systems.

 

Features

 

1.Designed to meet the following safety standards:

IEC 61010-1,-2-30 (CAT III 600V/CAT IV 300V Pollution degree 2);

IEC 61010-031 (Requirements for hand-held probes);

2.With auto-discharge function:

When an insulation resistance like a capacitive load is measured, electric charges stored in capacitive circuits are automatically discharged after the measurement. Discharge can be checked on the voltage monitor.

3.Backlight function to facilitate working at dimly illuminated location or at nighttime work.

4.Bar graph display;

5.Audible and visible LIVE circuit warning;

6.With Auto-power off function:

The instrument automatically will turn itself off if there is no function change or button press for 10 min to conserve battery power.

7.Auto-measurement and display of PI (Polarization Index), DAR(Dielectric Absorption Ratio);

 

 

Technical Indicators

  1. Measuring range and accuracy(Temperature, humidity;23±5℃,45-75%RH) <Insulation resistance tester>:
Rated voltage 250V 500V 1000V 2500V 5000V
Measure Range 0.1~100.0MΩ 0.1~99.9MΩ

80~1000MΩ

0.1~99.9MΩ

80~999MΩ

0.80~2.00GΩ

0.1~99.9MΩ

80~999MΩ

0.80~9.99GΩ

8.0~100.0GΩ

0.1~99.9MΩ

80~999MΩ

0.80~9.99GΩ

8.0~99.9GΩ

80~20000GΩ

Display range 0.1~100.0MΩ 0.1~1000MΩ 0.1M~2.00GΩ 0.1M~100.0GΩ 0.1M~2000 GΩ
Open circuit Voltage DC250V

+10%,-10%

DC 500V

+ 20%,-10%

DC 1000V

+ 20%,-0%

DC 2500V

+20%,-0%

DC5000V

+20%,-0%

Rated Current     1MΩ load

1mA~1.2mA

2.5MΩ load

1mA~1.2mA

5MΩ load

1mA~1.2mA

Short-circuit Current 5mA±0.5mA
Accuracy ±5%±3dgt ±5%±3dgt±20%

 

Voltage monitor for insulation resistance range:

30 – 600V (resolution 10 V): ±10%rdg±20V

This monitor is used to check whether electric charges stored no the equipment under test are discharged or not. The voltage value measured and displayed on the LCD is a reference value. Please note that the indicated value, when an external AC voltage is applied to the in strument, is not a correct value.

<Voltage measurement range>:

  DC Voltage AC Voltage
Measuring range ±30 — ±600V 30 — 600V(50/60Hz)
Resolution 1V
Accuracy ±2%rdg±3dgt

 

Display Liquid crystal display insulation resistance range:(Max.1200 counts) VAC/DC range: (Max.630counts) Bar graph: Max.36points DAR/PI value:Max.9.99 Time:Max.99.59
Low battery warning Battery symbol (in 4 levels)
Over range indication “OL” mark appears on insulation resistance range.
Auto-ranging Range shifts to upper range:1000 counts

Range shifts to lower range:80 counts

(Only on the insulation resistance range)

Auto-power-off The instrument will be powered off if there is no switch or button operation for 10 min.(This function does not work during a measurement.)
Altitude 2000m or less
Temperature & humidity range(guaranteed accuracy) 23℃±5℃/Relative humidity 85% or less(no condensation)
Operating temperature & humidity range 0℃ to 40 ℃/Relative humidity 85% or less (no condensation)
Storage temperature&humidity range -20℃ to ± 60%/ Relative humidity75% or less(no condensation)
Overload protection: Insulation resistance range AC 1200V/10sec.
Withstand voltage Voltage range:AC720V/10sec.

AC5160V(50/60Hz)5sec.(Between electrical circuit and enclosure)

Insulation resistance AC5160V(50/60Hz)5sec.(Between electrical circuit and enclosure)
Dimension 177(L)*226(W)*100(D)mm
Weight 1.9kg(battery included)
Power source 12.6V/6800mAh

 

  1. Current consumption (representative values at 12V of supply voltage)
Range 250V 500V 1000V 2500V 5000V VAC/DC
Output at Short-circuit 600mA 110mA
When rated current is outputted 650mA/0.25MΩ 800mA/0.5MΩ 1000mA/1MΩ 1350mA/2.5 MΩ 1350mA/5 MΩ
Output at open circuit 40mA 40mA 50mA 80mA 150mA
Stand-by 25mA
Backlight on Increased by 40mA

 

  1. Measurement time: for 25hours *under a load of 100MΩ on the Insulation resistance 5000V range.

 